Solar wire size and voltage drop calculator

Wire-size charts online disagree because they assume different temperatures, drop targets and lengths. This works it out from the standard copper values: resistance from the American Wire Gage law or the cable's mm² area, corrected for temperature, over the full out-and-back run. It sizes for voltage drop only; the cable must also be rated for the current.

Battery bank voltage, or a PV string's operating voltage (Vmp x modules).

For PV source circuits, building department plans use module Isc x 1.25. For an inverter, watts divided by battery voltage.

Length units

Your design target or the equipment manual's limit.

Copper resistance rises 0.393% per °C above 20 °C; cables in sun, conduit or engine bays run hot.

Cable sizes

Wire size for voltage drop

Smallest size that meets your target
4 AWG
Voltage drop at that size
0.33 V (2.78%)
Power lost in the cable
10.0 W
Voltage drop only. Check the cable's current rating (ampacity) in your electrical code too: short, high-current runs often need a larger cable than voltage drop alone requires.

Solid-conductor copper values; stranded cable can run slightly higher. Round-trip length (out and back) is used. Not a substitute for code-compliant design.

Every size on this run

18 AWG
71.38% · 257.0 W
16 AWG
44.89% · 161.6 W
14 AWG
28.23% · 101.6 W
12 AWG
17.75% · 63.9 W
10 AWG
11.17% · 40.2 W
8 AWG
7.02% · 25.3 W
6 AWG
4.42% · 15.9 W
4 AWG
2.78% · 10.0 W
2 AWG
1.75% · 6.3 W
1 AWG
1.39% · 5.0 W
1/0 AWG
1.10% · 4.0 W
2/0 AWG
0.87% · 3.1 W
3/0 AWG
0.69% · 2.5 W
4/0 AWG
0.55% · 2.0 W

Defaults and sources

Copper resistance
International Annealed Copper Standard: 10.371 ohm-circular mil/ft (0.017241 ohm-mm²/m) at 20 °C; temperature coefficient 0.00393 per °C at 20 °C; AWG No. 0000 = 0.4600 in and No. 36 = 0.0050 in with sizes in geometric progressionNBS Handbook 100, Copper Wire Tables (National Bureau of Standards, now NIST) · checked Nov 10, 2026
Maximum circuit current
Module Isc x 1.25 per source circuit; conductors sized at a further 1.25Los Angeles County Public Works, Solar PV Standard Plan, Comprehensive · checked Nov 10, 2026

How the calculator works

Resistance per length comes from the International Annealed Copper Standard (10.371 ohm-circular mil per foot, or 0.017241 ohm-mm² per metre, at 20 °C), divided by the conductor area. AWG areas follow the American Wire Gage law, with No. 0000 at 0.4600 inch and No. 36 at 0.0050 inch.

Resistance is raised by 0.393% per °C above 20 °C. Voltage drop is current times resistance over twice the one-way length (out and back); power lost is drop times current. The pick is the thinnest listed size whose drop is at or under your target.

Solar wire sizing: common questions

What size wire for 30 amps at 12 volts?

For a 20-foot run (40 feet out and back) at a 3% drop target and 50 °C conductor temperature, 4 AWG keeps the drop to about 2.8%. At 24 V the same run needs 6 AWG, and at 48 V only 10 AWG, because the allowed drop in volts doubles each time the voltage doubles.

Why do 12 V systems need such thick cable?

The same power at a lower voltage means more current, and a 3% target allows fewer volts of drop. A 3,000 W inverter draws 250 A at 12 V but 62.5 A at 48 V, and at 12 V a 3% drop is only 0.36 V.

Does temperature change the wire size?

Yes. Copper's resistance rises 0.393% for every °C above 20 °C, so a cable at 60 °C has about 16% more resistance than the same cable at 20 °C. That can push a borderline run up a size.

Is voltage drop the only thing to check?

No. The cable must also be rated to carry the current safely (its ampacity), which depends on insulation, installation and your electrical code. A 5-foot 48 V run at 62.5 A passes a 3% drop test with 12 AWG but needs a much larger cable for current; check the code table.