Solar string sizing calculator

A string has to pass three checks, and most calculators only do the first: on the coldest morning its open-circuit voltage must stay under 600 V (on homes) and the inverter's maximum; on the hottest afternoon its operating voltage must stay inside the inverter's MPPT range; and its current must fit the input. Enter your module datasheet and inverter specs to get the valid range of modules per string.

Module (from the datasheet)

Negative, usually -0.24 to -0.30 %/°C for modern modules. If the datasheet gives mV/°C, divide by Voc and multiply by 0.1.

Use the Vmp coefficient if listed; the Pmax coefficient is a close, slightly conservative stand-in.

Site

The coldest temperature at dawn at your site; building departments usually reference ASHRAE's extreme annual minimum.

Roof-mounted cells run well above air temperature on a hot, still afternoon. Use your design value.

Inverter (one MPPT input)

From the inverter datasheet; compared with module Isc times strings in parallel.

System voltage limit

Your design

String check

Valid range
4-12 modules
Maximum modules per string
12
Minimum modules per string
4
Cold Voc per module
49.1 V
Hot Vmp per module
32.4 V
Cold Vmp per module
41.4 V
Your string's cold Voc (11)
540.0 V: Passes
Your string's hot Vmp
356.8 V: Passes
Your string's cold Vmp
455.8 V: Passes
Short-circuit current into the MPPT (1)
13.9 A: Passes
Maximum circuit current for wire and fuse sizing (Isc x 1.25)
17.4 A
Table method instead (factor 1.14)
11 modules

Design aid only. Follow the module and inverter manuals and the code edition your building department enforces; a licensed designer must sign off the string plan.

Defaults and sources

Maximum string voltage (NEC 690.7, coefficient method)
Modules in series x [Voc + (lowest expected ambient temperature - 25) x Voc temperature coefficient]; must not exceed 600 V on one- and two-family dwellings or the inverter's maximum input voltageLos Angeles County Public Works, Solar PV Standard Plan, Comprehensive (one- and two-family dwellings) · checked Nov 10, 2026
Maximum circuit current
Module Isc x 1.25 per source circuit; conductors sized at a further 1.25Los Angeles County Public Works, Solar PV Standard Plan, Comprehensive · checked Nov 10, 2026
Table correction factor (when no coefficient is given)
1.12 when the lowest expected temperature is -5 C or warmer; 1.14 from -6 C to -10 CCity of Lathrop, Solar PV Standard Plan, Simplified Central/String Inverter Systems (CEC 690.7) · checked Nov 10, 2026

How the calculator works

Cold Voc per module is Voc x [1 + coefficient x (lowest temperature - 25) / 100], the NEC 690.7 coefficient method used on building department standard plans. The maximum string length is the lower of the system limit and the inverter's maximum DC voltage, divided by the cold Voc, rounded down.

Hot Vmp per module uses the Vmp (or Pmax) coefficient at the hottest cell temperature; the minimum string length is the MPPT minimum divided by hot Vmp, rounded up. Cold Vmp is checked against the MPPT maximum. Short-circuit current into the MPPT is Isc times the strings in parallel, compared with the inverter's input rating; the maximum circuit current for sizing conductors and fuses is Isc x 1.25 per source circuit.

Where the module datasheet gives no voltage coefficient, standard plans use a table factor instead: 1.12 for lows of -5 °C or warmer and 1.14 from -6 °C to -10 °C. The calculator shows that result for comparison when your low is in that range.

Solar string sizing: common questions

How many solar panels can I put in one string?

Divide the voltage limit by each module's open-circuit voltage at your coldest temperature and round down. A module with a 45 V Voc and a -0.26 %/°C coefficient reaches about 49.1 V at -10 °C, so 12 fit under 600 V; at -20 °C it reaches about 50.3 V and the limit drops to 11.

Why does string voltage rise in cold weather?

A module's voltage coefficient is negative, so its voltage rises as it gets colder. Datasheet Voc is measured at 25 °C; at -10 °C the same 45 V module produces about 9% more, which is why string sizing starts from the coldest expected morning, not the datasheet figure.

What is the minimum number of panels per string?

Enough that the string's operating voltage stays above the inverter's MPPT minimum on the hottest day. With a 37.5 V Vmp and a -0.30 %/°C coefficient, each module drops to about 32.4 V at a 70 °C cell temperature, so a 120 V MPPT minimum needs at least 4 modules and a 200 V minimum needs 7.

Is the 600 V limit the same for every building?

Building department standard plans for one- and two-family dwellings cap PV DC circuits at 600 V or the inverter's maximum input voltage, whichever is lower. Larger buildings may be allowed higher voltages under the code edition in force; check with your building department.

What if the module datasheet has no voltage temperature coefficient?

Use the code's table factor instead. California standard plans apply 1.12 when the lowest temperature is -5 °C or warmer and 1.14 from -6 °C to -10 °C. The table is more conservative: at -10 °C it allows 11 of the 45 V modules under 600 V, against 12 with the coefficient.