Inverter battery backup calculator

The usual formula (Ah x 12 V x efficiency / watts) assumes the battery gives its full rating at any load. A tubular battery rated at C20 does not: in the Exide-made MTU-200 datasheet it gives 90% of its rating over 10 hours but 63% over 3 hours. So a 150 Ah battery runs a 300 W load for about 3 hours, not 4.8. Add your appliances to see your real backup.

What will run on the inverter?

Example watts: replace them with the figure on each appliance's label or box. Set the count to 0 to leave an item out.

  • Ceiling fan

  • LED bulb

  • LED tube light

  • Wi-Fi router

  • LED TV

  • Room cooler

  • Refrigerator

Battery and inverter

The rating is printed on the battery, e.g. '150Ah @ C20'. Most home inverter batteries are C20; solar tubulars are often C10.

12 V takes one battery; 24 V takes two in series, 48 V four. Check the inverter's label.

An assumption: home inverter makers we checked don't publish it. Use your datasheet's figure if it has one.

Older lead-acid batteries hold less. If a new battery's backup has fallen by a quarter, enter 75.

100% runs until the inverter's low-battery cut. Exide and Microtek rate cycle life at 80%; lower means fewer hours today but more years.

On the label or spec sheet; the Luminous Zelio+ 1100 is 900 VA and 756 W.

Your backup time

Total load
296 W
Backup time
3 h 04 min
What the flat formula says
4 h 52 min
Difference
37% less
Current drawn from the battery
30.8 A
Capacity the battery gives at this current
94 Ah (63%)
Inverter load
39% of 756 W
Battery needed for your target (4 h)
183 Ah per battery

Lead-acid backup is read from a 200 Ah tubular datasheet's discharge table scaled to your Ah, to 10.5 V at 27 °C. Lithium is treated as giving its full rating up to its current limit. Hot weather, old batteries and a partly charged battery all change real backup.

Backup time at other loads (this battery)
LoadBackupWhat the flat formula says
100 W13 h 35 min14 h 24 min
200 W5 h 23 min7 h 12 min
300 W3 h 00 min4 h 48 min
400 W1 h 57 min3 h 36 min
500 W1 h 20 min2 h 53 min
600 W0 h 58 min2 h 24 min

Defaults and sources

Tubular battery discharge table (used for lead-acid backup time)
12 V 200 Ah @ C20 tall tubular, to 1.75 V/cell at 27 °C: 82.1 A for 1 h, 41.7 A for 3 h, 29.0 A for 5 h, 18.0 A for 10 h, 10.0 A for 20 h (41%, 63%, 73%, 90% and 100% of the C20 rating)Marvel Tech MTU-200 Premium (made by Exide) technical data sheet, discharge data · checked Nov 22, 2026
Cross-check against a second tubular datasheet
12 V 200 Ah @ C20 tubular (tested to IS 13369:1992): 400 W (33 A) backup to 10.5 V is 4 h 15 min; capacity 200 Ah at 20 h, 146.6 Ah at 5 h, 126.2 Ah at 3 h, 88.0 Ah at 1 h. The calculator's table gives about 4 h 08 min for the same 33 AWelion 12V200Ah tubular battery data sheet, electrical performance · checked Nov 22, 2026
Exide Home InvaTubular IT500 (150 Ah preset)
150 Ah @ C20, 12 V tall tubular; 1,200 cycles at 80% depth of discharge; IT650 is 180 Ah @ C20Exide Industries, Home InvaTubular inverter battery range, technical specifications · checked Nov 22, 2026
Lithium (LiFePO4) inverter battery preset
12.8 V, 100 Ah, 1.28 kWh; discharge cut-off 11.2 V; 50 A standard and 150 A maximum continuous discharge; more than 4,000 cycles at 80% depth of dischargeMicrotek, Lithium Ion 100Ah Battery, specifications · checked Nov 22, 2026
Inverter rating preset (900 VA)
Luminous Zelio+ 1100: 900 VA, 756 W, pure sine wave, one 12 V batteryLuminous Power Technologies, Zelio+ 1100 technical specifications · checked Nov 22, 2026
What a 900 VA inverter is sold to run
Fan, CFL, tube light, LED bulb, mixer (up to 600 W), room cooler (up to 200 W), LED TV (up to 49 in), inverter refrigerator (up to 260 L), desktop computer, deskjet printerV-Guard Industries, Prime 1050 (900 VA, 12 V) specification sheet · checked Nov 22, 2026
Inverter efficiency (battery mode): assumption
80% by default. None of the Luminous, Microtek or V-Guard 12 V home inverter pages checked publishes a battery-mode efficiency figure, so this is an input: replace it with your datasheet's figureEarth Energy Log assumption; checked Luminous Zelio+ 1100, Microtek Luxe SW 1200, V-Guard Prime 1050 · checked Nov 22, 2026

How the calculator works

Battery current is your load divided by the inverter efficiency and the battery voltage (12 V per lead-acid battery, 12.8 V per LiFePO4 battery). For example, 300 W at 80% is 375 W from a 12 V battery, or about 31 A.

For tubular batteries the calculator finds how long a 200 Ah C20 battery lasts at the same current per Ah, by interpolating its datasheet's discharge table (82.1 A for 1 hour down to 10.0 A for 20 hours, to 1.75 V per cell). A C10-rated battery is converted to C20 using the same table: 10 hours x 18.0 A is 90% of 200 Ah. Checked against a second datasheet: at 33 A on 200 Ah it gives 4 h 08 min against the measured 4 h 15 min.

Backup time is then multiplied by battery health and the share of capacity you allow to be used. 'Battery needed' searches for the smallest Ah that reaches your target hours with the same settings.

Inverter battery backup: common questions

How many hours will a 150Ah battery last?

For a 150 Ah tubular battery rated at C20 on a 12 V inverter at 80% efficiency: about 13.5 hours at 100 W, 5.4 hours at 200 W, 3 hours at 300 W, 2 hours at 400 W and 1 h 20 min at 500 W. The flat formula would say 14.4, 7.2, 4.8, 3.6 and 2.9 hours.

Why is my backup less than the formula says?

Because a lead-acid battery's Ah rating is measured over 20 hours (C20). Drawn faster, it delivers less: the Exide-made MTU-200 datasheet gives 90% of the rating over 10 hours, 73% over 5 hours and 63% over 3 hours. Inverter losses, age and heat take more.

Is a C10 battery better than C20?

For the same printed Ah, yes: a 150 Ah C10 battery holds about as much as a 167 Ah C20 one, because C10 is measured at the faster 10-hour rate. At 300 W it lasts about 3 h 28 min against 3 hours for 150 Ah C20.

Does a lithium inverter battery give more backup?

Per rated Ah, at higher loads. A 100 Ah LiFePO4 battery outlasts a 150 Ah C20 tubular above about 225 W in this calculator (3 h 25 min against 3 hours at 300 W) because its capacity does not fall with current the way lead-acid does. At light loads the bigger tubular still lasts longer.

What battery do I need for 4 hours of backup?

On a 12 V inverter at 80% efficiency: about 124 Ah (C20 tubular) for 200 W, 185 Ah for 300 W and 247 Ah for 400 W. LiFePO4 needs 79, 118 and 157 Ah. Above about 300 W a 24 V inverter with two batteries is the better design.